Generator Protection
1- Rotor malfunctions
In the event of more than one
ground fault in the circuit of the rotor (field), magnetic imbalance occurs and
then vibrations occur in the machine, which makes the detection of ground
faults in the circuit of the rotor of fundamental importance, and Figure (1)
shows the model used, which uses constant current and the principle of dividing
the voltage between R2 and R1 as two
constant resistors (often taken for the excitation circuit at a rate of 250
volts), noting that RN It is a resistance that changes with the change of
voltage applied to it (traditionally 45 kΩ at 60 V and 4.7 at 150 V).
Figure (1): Diagram of a system for the protection
against ground faults of the field circuit
When the field circuit (excitation
) is connected, a voltage will appear between point M and the ground (the
voltage value depends on the voltage of the excitation circuit and the failure
point on the field circuit, and the value of the voltage VMO is the highest possible value if the failure is
on any side of the field circuit and the point of the field circuit, at which
point (VMO=0) is called the NULL POINT, and in the case of:
R2 = R1 +
RN
The idle point in the center of the field coil
and the DC relays will detect abnormal voltage values of V0 and then the rotor
failures.
2- Different ways to prevent the birth
Figure (3) shows all the
prevention methods discussed that are designed to detect the faults that occur
to the generators, in addition to some preventive measures that are taken, such
as lightning arresters, which are connected between the phases of the entrances
and the star point of the coil and the ground and its function is to reduce the
stresses that the coils are exposed to due to sudden weather changes.
In the event of an increase in
the turbine speed, the voltage increase unit works to suppress and reduce the
field, and this importance also appears for the faults that occur in the
voltage regulator and the excitation system, while in the water units, voltage
increase relays are used with a time lag with high speed relays, while in turbo
generators, the use of instantaneous voltage increase relays is the best
choice.
Thermal relays
use protection against load surges that cause
an unacceptable increase in temperatures, and these relays intervene to operate
when the coil to be protected reaches the limits of the temperatures designed
for and the transformer has the same thermal curve as the generator with the
compatibility in the time constant of the generator. The relay is able to
withstand the increase in load for a short time, so the load of the generator
can increase to its highest thermal capacity.
As for the
thermal current surge relays, which have intermediate
time constants, they are used in the output circuits of the voltage regulator,
but in the event of a permanent positive or negative excitation as a result of
a failure in the regulator, the generator is converted to the use of a manual
regulator.
As for the negative sequence relays, they are used in the case of a single-phase load of a
three-phase generator higher than the allowable increase, and the same relay is
able to perform thermal protection for the moving part of the generator,
because in the event of an asymmetric load of the machine, different currents
are generated in the phase and with a double frequency in the moving part,
which leads to a harmful increase in the heat to which the heart is exposed.
Figure (2): Locations of the protective devices for
the fixed and moving part and the circuit of the main motor
As for the relays that operate with
the least capacitive reactor , they are used in generators
when there is a danger to that, and this relay is linked to the voltage surge
relay and is not delayed in time in a way that allows that when the process of
self-excitation begins, both relays start working and send the signal to the
circuit breaker of the generator to work immediately, and during the second
output, a relay of a late type is connected, and when the time delay ends, it
causes the closure of the hydrogenerators and suppression of the field for the
turbogenerators, with the possibility of giving permanent excitation For
asynchronous operation. This relay also
has the ability to detect harmonies or minor malfunctions that occur in the
excitatory circuit. For such failures, either the generator is immediately out
of service or stays in the network while trying to restore the network to
synchronization again.
Figure (3) shows the diagram (X-R) of the less
capacitive reactant when it is:
XD is the synchronous reactor of the generator
X'd is the trans-generator reactor
a, b constants for adjustment
Figure (3): Diagram showing the geometric location
of the operation of a less capacitive reactor in the negative reactor region on
the diagram (R-X)
Reverse power relays
stop the generator when the generator is operating
as a motor at full speed due to a turbine malfunction and the generator is
still connected to the grid, but in some systems a high sensitivity directional
power relay is used that is set at a small value instead of using a reverse
power relay.
In order to remove the currents
that occur in the loading piles, at least one loading substrate is isolated
from the ground with its auxiliary piping system, and then faults in the
insulation or shortages in the circuit are detected by the presence of an
object connected to the current protection system in the loading piles, which
determines the current that flows directly in the loading piles, and is often
applied in two stages.
0 Comments