UPS Operation SOP
To provide a standardized procedure for safe and reliable operation of UPS systems, ensuring uninterrupted power supply to critical loads.
2. Scope
Applicable to all online, line-interactive, and offline UPS systems in data centers, hospitals, industrial plants, or commercial buildings.
3. Responsibilities
- Operators: Monitor UPS operation, follow procedures, and log readings.
- Maintenance Team: Conduct preventive maintenance and troubleshooting.
- Supervisors: Authorize switching between mains, UPS, and bypass modes.
4. Safety Precautions
- Only trained and authorized personnel should operate the UPS.
- Wear PPE (insulated gloves, safety shoes, eye protection).
- Do not bypass UPS protection circuits.
- Never operate UPS in wet or humid conditions.
- Ensure proper ventilation around UPS and battery banks.
- Be aware that UPS output remains live even when mains fails.
- During maintenance, follow lockout-tagout (LOTO) procedures.
5. Pre-Operation Checks
1).. Visual Inspection:
- Check UPS for alarms, warning lights, or physical damage.
- Ensure batteries are free from swelling, leaks, or corrosion.
2).. Power Sources:
- Verify input (mains) voltage and frequency are within limits.
- Check generator readiness (if connected).
3).. Indicators & Alarms:
- Confirm UPS is in normal mode (mains supply with battery charging).
- Ensure no faults are active on display/control panel.
6. Operating Modes & Procedures
6.1 Normal Operation (Mains Available)
- UPS receives power from mains supply.
- Battery remains on float charging mode.
- Load is continuously supplied with conditioned power.
- Operator monitors:Input voltage, output voltage, frequency, load %, and battery status.
6.2 Power Failure (Mains Supply Lost)
- UPS automatically switches to battery mode without interruption.
- Critical load continues to run on battery power.
- Operator should:
- Verify UPS alarms and battery runtime.
- Inform control room/supervisor.
- Start generator if backup is available.
6.3 Generator Synchronization
- Once generator stabilizes, UPS automatically shifts to generator input.
- Battery resumes charging mode.
- Monitor:
- Generator voltage and frequency.
- UPS input/output readings.
6.4 Returning to Normal (Mains Restored)
- UPS automatically transfers input back to mains supply.
- Battery charging resumes.
- Monitor all indicators to ensure smooth transition.
6.5 Manual Bypass (for Maintenance)
- Inform supervisor and control room.
- Ensure load can tolerate transfer without risk.
- Switch UPS to manual bypass mode.
Load is supplied directly from mains (not protected by UPS).
- Perform maintenance as required.
- Return UPS to normal operation after checks.
7. Monitoring During Operation
-
Continuously monitor:
- Input voltage & frequency
- Output voltage & load percentage
- Battery status (charging/discharging/health)
- Alarms and fault indicators
-
Record all readings in UPS logbook at defined intervals.
8. Fault Handling
UPS Alarm or Fault Condition:
- Identify alarm code from display/control panel.
- If critical, transfer load to bypass supply.
- Inform maintenance team immediately.
Overload Condition:
- Disconnect non-critical loads.
- If overload persists, UPS may transfer load to bypass.
Battery Low/Failure:
- Reduce load to extend runtime.
- Shut down non-essential loads until mains or generator is restored.
9. Shutdown Procedure
- Inform control room and end-users before shutdown.
- Switch UPS to bypass mode (load supplied by mains).
- Turn off UPS output breaker.
- Turn off UPS input breaker.
- Disconnect battery bank (if long-term shutdown).
- Record shutdown in the logbook.
10. Maintenance
- Daily: Check UPS panel indicators, alarms, and log readings.
- Monthly: Verify battery connections, ventilation, and environment.
- Quarterly: Test UPS transfer (mains → battery → mains).
- Annually: Full preventive maintenance (battery test, cleaning, calibration).
11. Documentation
- UPS Logbook: Record input/output voltages, load %, battery status, and alarms.
- Fault Reports: Document cause, action taken, and resolution.
- Maintenance Records: Scheduled inspections and servicing details.
12. Best Practices
- Never overload the UPS beyond rated capacity.
- Test batteries periodically under load.
- Keep UPS room temperature within manufacturer’s recommended range.
- Maintain clear space for ventilation.
- Regularly train staff on UPS operation and emergency handling.
0 Comments