Supply Systems & Transmission of Electrical Energy

 

Supply Systems & Transmission of Electrical Energy

  1- Choice of Supply Circuits

1-1 Feeding with a voltage equal to the generator voltage

The choice of the electrical diagram for power plants depends on the nature of the loads and the importance of continuous feeding to them, as well as on the flexibility in operation and the ease of performing maintenance for electrical equipment, and there are many executed diagrams, but in main forms that can be considered as one of the basic plans or a mixture of them. These schemes are divided from one simple radiative circuit to several overlapping circuits to maintain the continuity of electrical supply, which means an increase in the use of protection systems and thus an increase in economic cost with complexity in operation.a

Figure (1) shows several systems of buses, which are connected to feeders with a voltage equal to the generation voltage, and part (a) of the figure represents the simplest electrical diagrams that can cut off the feed from the loads for a while. There is a circuit breaker for the generator, as well as on each feeder to deliver loads and protect in case of shortage. Each feeder also has a disconnecting switch and its purpose is to protect back up. When servicing the open-ended cutting device on the feeder. Most of the time, this switch connects to the ground to protect and leak any remaining charge.

 In Part B of the figure, two rods, cutting devices and switches are used for loads that require continuous feeding, and maintenance of the generator or rod cutting device can be performed without interruption to feed and provide protection for people who perform maintenance operations.

 Parts (c) and (d) are less elastic than (b).

When using two rods for distribution, a selector breaker can be connected to select the feeder rod, as well as it works as a backup protection in case of failure of the feeder cutting device.


 

Figure (1)

 

A bus-tie breaker is used when  feeding more than one generator so that each generator ends up on a part of the rod to avoid the difference in voltage in value and angle on the two parts of the rod during reactor when the power is interrupted from one of the generators, which causes circulating currents in the circuit  .

Parts (f) and (e) show a more sophisticated scheme.

In all the above schemes, it is necessary to have current and voltage transformers that feed the protection devices. Also, measuring devices for electrical quantities such as current and voltage and control units that enable the system operator to connect or disconnect any electrical equipment. It is also necessary to have  a ground bus to ground the feeders during maintenance or repair. There may also be  fire walls between the parts of the rods to prevent the fire from spreading to all parts.

 

1-2 Feed Through Voltage Lifting Transformers

In this case, the transformers are used to raise the generating voltage, and there are several diagrams between them Figure (2) where each generator can be connected to a transformer and then to a feeder, part (a) of the figure. Or the generators are fed on a rod from which feeders with a voltage equal to the generation voltage and the other on transformers to raise the voltage, part (b) of the figure, and part (c) of the same figure shows a diagram that allows the continuity of the feed all the time, while Figure (D) allows flexibility in operation with the use of a number of Less than the cut-off devices for state (C).

 

2- The importance of electric power transmission lines :

Transmission lines are used  to transmit electrical energy from places of generation, whether hydrothermal - gas- nuclear plants or others to the places of electrical load centers. Lines - called "tie lines" - are also used  to connect electrical power systems.

 

3- Systems and voltage of electrical power transmission lines :

3.1 Low voltage and DC transmission

Transmission by low voltage direct current

3.1.1 Radial system

This is the first method used to transmit electrical energy, and Figure (3) shows a diagram of the system and determines the area of the cable section based on the value of the current allowed to pass through it (Current carrying capacity ), as well as the changes in voltage at electrical loads not exceeding a certain percentage (5% - 6%) (Voltage regulation). The main disadvantage of this system is the interruption of the supply of loads to a distributor if it malfunctions.


Figure (2)

 


Figure (3)

 

 

 

3.1.2 Ring     system

Figure (4) shows the diagram of this system, in which it is possible to avoid interruption of the supply of loads in case of a malfunction in the distributor, where the feed is done from the other side, as well as the loop can be fed by more than one generator, as shown in Figure (5).


Figure (4): Single-source ring feeding system

 


Figure (5): Ring feeding system from multiple sources

 

3.1.3   Wire system

In the case of large electrical power transmission, this requires cross-section transmission lines and therefore a high cost. Therefore, a wire convergence system can be used as shown in Figure (6) where the N-1 circuit is fed  through the first generator, and  the N-2 circuit is fed  through the second generator. Only the tie line of the two generators is connected to each other and to the ground. Therefore,  the line carries N.  The difference in current can be reduced to a certain extent, as by reducing the cross-sectional area, the resistance of the wire will increase, thus increasing the voltage difference and increasing the value of the earth potential, and most often an electric line N with a cross-sectional area equal to half of the cross-section area of the outer lines (1-2) is used.


Figure 6: Tri-wire system

 

 In order to determine the percentage of savings in the material connected in a three-wire system to a two-wire system, it is assumed that:

V:  voltage between the wires in 2 – wire case I and between the outer and the neutral in 3 - wire case II

P: Power transmitted

R1: Resistance per unit length for case I.

R2: Resistance per unit length of outer wires in case II

 

Resistance of the neutral     = 2 R 2 per unit length

I in 2- wire case                   = P/V

Power loss = 2 I 2 R = 2 (P/V) 2  R1

I in 3- wire case, and assume equal loads ,i.e I1 = I2, I through N=0

                        I = P / (2V)     

Power loss = 2 ( P /2V)2 R2

For equal power loss :

2 / (P/V )2 R1 = 2 ( P/2V)2 R2

        R2 = 4 R1

Cross section of the outer is ¼ of that in the 2- wire

Copper ratio:

3 – wire = (2 x  ¼ ) + (1/2  x ¼ ) = 5   = 31.25

2 – wire                   2 x 1                16

 

Reduction in case of using 3 – wire = 68.75 %

 

If the neutral has the some cross section as the outer, the ratio is :

3 – wire = (2 x ¼ ) + (1 x ¼ ) = 3   = 37.5 %

2 – wire                   2 x 1             8

 

Reduction in case of using 3 – wire = 62.5 %

 

If the loads on the outer lines are not equal in a three-wire system, the savings will be reduced. Therefore, it is preferable that the loads are the same in the two circuits.

 

3-2 Advantages of High Voltage

If the voltage is increased by a multiplier of m, where m is greater than one, the amount of material used in the transmission lines will decrease  by 1/m2 for the same value of the transmitted power and the loss of electrical power. If the voltage increases by the multiplication factor  of m, the current will decrease by  a multiplier of 1/m for the same value of the transmitted power, and since the loss of power is equal to the resistance multiplied by the square of the current, it is for the same value of the lost power (Ohmic loss) the  resistance M2 will be the  previous value and therefore the material will be  only 1/m2. However, with the increase in the voltage of the transmission lines, it is necessary to use towers, insulators and cutting devices in higher cost, so a technical and economic study must be done to determine the optimal transmission voltage value  according to each system.

 
3.2.1 Transmission by alternating current

The use of AC current allows the possibility of raising the voltage using electrical power transformers, and there are many transmission systems that are explained in the following parts:


3.2.1.1 Single-sided system - two or three wires

Single phase Two and three - wire systems

Figure (7) shows the different cases used in the transfer, where the secondary file of the transformer is shown in the figure. In this case, too, a three-wire transmission is distinguished from a two-wire transmission as is the case when using DC current.



Figure (7) 


 

3.2.1.2 Bifacial system - three or four wires

Bifacial voltage generators have two orthogonal coils, so the electric motive force generated in the two coils is perpendicular to it, and Figure (8) shows a three- and four-wire system where the coils are finally divided into two equal parts  mid point and the division points are connected.  Transportation using this system is very limited.


Figure (8): We are oppressed bifacial

3.2.1.3 Three-Phase System - Three or Four Wires

The tri-wire system represents the vast majority of transmission systems. And connecting files in the form of a star or delta, Figure (9).


Figure (9): Three-Sided System

 

 In order to compare the amount of material conducting the transmission lines in this case and the transmission condition using constant current – 2 wires, it is assumed that the maximum value of the voltage between the line and the ground in both cases is equal.

 

Let E voltage between conductors in d-c. , I is current

Power = E I

Loss = 2 R2 I

R : resistance of each wire per unit length for DC system

 

For star connected 3 phase, maximum voltage E,

r.m.s value = E / Ö 2

I’ is the r.m.s. value of the line current

Power = 3/Ö 2  E I’ cos f

Loss = 3 R’ I’2

R’ : resistance per wire for 3 phase system

 

For same transmitted power:

E I = 3/Ö 2  E I’ cos f

 

And same power loss:

2 R I2  = 3 R’ I’2

 

Hence R = R’ / ( 3  cos2 f )

 

Each wire in the 3 phase system has a cross section = 1 / ( 3  cos2 f ) of that in the DC system. As there are 2 conductors in the DC system and 3 in the 3 phase system , then the DC system requires (3/2) / (1/  ( 3  cos2 f )) = 0.5 as much material.

 

3.2.1.4 Alternating Current Six Phase Systems

The hexagonal system consists of two connected triangular systems so that each face of one of the triangular systems is dislodged at an angle of 180 degrees from the opposite face in the second triangular system. Figure (10) shows a hexagonal system consisting of two sets of coils connected to a delta, part (a) shows the state of a hexagonal system with 6 wires, and part (b) a hexagonal system with 7 wires as well as giving the shape of the voltage vectors. 1) Shows a comparison between the different systems of the AC state by imposing the same loads the same voltage value between the wires and the same value of the cross-sectional area and the values attributed to the case of one face with two wires.

 


Figure (10)

 

Table (1)

 

Voltage Drop (Approximate)

Power Loss

Amount of conductor

Type of AC system

1.0

1.0

1.0

2- wire

Single Phase

0.25

0.25

1.5

3-wire

0.5

0.5

1.5

3-wre

Two Phase

0.25

0.25

2

4-wire

0.25

0.25

2.5

5-wire

0.167

0.167

1.5

3-wire *

Three Phase

0.5

0.5

1.5

3-wire **

0.167

0.167

2

4-wire

0.042

0.042

3

6-wire

Six Phase

0.042

0.042

3.5

7-wire

* Star voltage same as single phase

** Delta voltage same as single phase

3.2.2 DC Transmission

Recently, the use of continuous voltage transmission lines, although it is still relatively limited, has increased, due to the many features of constant current, as well as to the advances in power electronics devices and systems that convert variable current into constant current and vice versa, and the first use of these lines was for cables extended under the seawater, and there are overhead lines. One of the advantages of these lines is the lack of loss in the transmitted power, as there is no loss in reactance due to its absence in the first place, as well as the loss of voltage due to the same reason as before. There are no problems of electrical equilibrium no matter the length of the electrical line, as is the case when the line carries a declining current because the current is a constant value. Variable current to constant current conversion plants and vice versa also cause harmonic contamination  in the areas surrounding these stations in the network.

 

4- Multiple systems for feeding electrical networks

Figure (11) shows some feeding diagrams for the transmission networks, and part A represents the fully sectionalized supply on the rails  and is characterized by a high degree  of reliability  and flexibility  , and the feeding is not interrupted if there is a failure or maintenance in one of the lines one circuit where the other circuit feeds and part (B) represents the feeding through a looped in supply loop In this case, fewer cutting devices are used for case A, and also in this case, it is possible to continuously feed loads even in case of failure or maintenance in one of the lines, but the operation of the relays is more difficult than in case (A).

The scheme in part C is less costly than in case A and slightly lower than in case B and is used in case if the feed cuts are briefly harmless. Adjusting the operation of relays is more difficult and removing a short circuit may require more than one cutting device, and generally in large networks it is a mixture of the previous schemes.


 

Figure (11)

 

 

 

 

Post a Comment

0 Comments