In electrical design, the distribution of sockets is not just drawing circles on the walls...
Each socket you specify by:
✅ Usage
✅ Device shape
✅ required current
✅ and the place itself has moisture?
And no children? And no high load?
This is a
practical and short guide to all types of socket that you will need in your
design, with numbers and requirements 👇
🔌 1. Single Socket – Single (13A/16A)
Usage:
Light Appliances – Chargers – Fan – Laptop
Rated
current: 13–16A
Capacity:
180 – 250 VA
Observations:
✅ the most common
✅ Rides at a height of 30 cm or 105 cm
depending on the function
✅ Delivers on MCB 16A
✅ The American code calculates 180 VA
automatically if there is no specific device
---
🔌 2. Double Socket – Double
Usage:
Two devices side by side (TV + receiver for example)
Rated
current: 13–16A × 2
Capacity:
360 – 500 VA
Observations:
✅ Suitable for offices and bedrooms
✅ You can't put heavy loads on it
without distribution
---
🔌 3. Switched Socket – With Key
Usage:
Appliances that need constant disconnection such as a microwave or heater
Current:
13–16A
Capacity:
250 VA
Observations:
✅ Gives you quick manual control
✅ Required in kitchens according to
the Saudi code and NEC
---
🔌 4. Socket with USB Ports
Usage:
Direct charging for mobile – headphones – tablet
Current:
13A+2.1A USB
Capacity:
180 VA + 10–15 VA
Observations:
✅ Do not increase the total load
✅ It saves space and increases
efficiency
---
🔌 5. Waterproof Socket – Waterproof
(IP44/IP55)
Usage:
bathrooms – balconies – laundry rooms
Current:
13–16A
Capacity:
250 VA
Observations:
✅ GFCI is required in the American
code
✅ RCCB in Saudi Arabia and UAE
✅ IP44 minimum – IP55 is preferred if
it has direct spray
---
🔌 6. Floor Box Socket
Usage:
Meeting rooms – open halls – offices
Current:
13–16A
Capacity:
250 VA
Observations:
✅ Installed in the ground with cover
✅ Withstands weight and movement
✅ Important in modern designs
--
🔌 7. High Current Socket (20A)
Usage:
Air conditioner 1.5 tons – medium appliances
Current:
20A
Capacity:
2000 – 2400 VA
Observations:
✅ Independent circuit
✅ Cable of at least 4 mm²
✅ Separate MCB
---
🔌 8. High Current Socket – (32A)
Usage:
Heaters – Large Air Conditioners
Current:
32A
Capacity:
3500 – 4000 VA
Observations:
✅ Does not ride with regular sockets
✅ Special connection and special
cutter
---
🔌 9. High Current Socket – (40A)
Usage:
Electric oven – water pump – industrial washing machines
Current:
40A
Capacity:
5000 – 6000 VA
Observations:
✅ Does not ride in common circuits
✅ Connects with at least 6 mm² cable
---
🔌 10. 3-Phase Industrial Socket –
Three-Phase
Usage:
Pumps – Machines – Industrial Devices
Current:
20A to 63A (3Φ)
Capacity:
8000 – 25000 VA
Observations:
✅ Requires MCCB
✅ An emergency key is needed soon
according to the industrial code
---
🔌 11. Childproof Socket – Protect for
Children
Usage:
Children's rooms – schools – nurseries
Current:
13A
Capacity:
180 – 200 VA
Observations:
✅ Required in NEC as Tamper-Resistant
(TR)
✅ Heavily used in educational and
service projects
Code Notes:
✅ The US code calculates each general socket with 180 VA (NEC 220.14(I)) if the load is not specified
✅ The Saudi and Emirati codes impose RCCB protection for any place where there is moisture or critical devices
✅ Socket distribution must be given every 1.8 m maximum in the walls (NEC 210.52)
✅ In kitchens: every 1.2 meters socket on marble