MCC (Motor Control Center) Circuits Design

 MCC (Motor Control Center) Circuits Design

MCC (Motor Control Center) Circuits Design refers to the design of the electrical circuits within a Motor Control Center. MCCs are centralized systems used for controlling multiple motors from a single location. They house various electrical components such as circuit breakers, contactors, overload relays, starters, fuses, and wiring. The purpose of MCC circuits design is to ensure that motors and their associated equipment are safely and efficiently controlled and protected. The design of MCC circuits focuses on power distribution, control wiring, protection, and monitoring of motors and other electrical equipment.

Steps Involved in MCC Circuits Design:


1. Define the Scope and Requirements

  • Number of Motors: Identify how many motors will be controlled from the MCC.
  • Motor Ratings: Determine the rating of each motor (power, voltage, current, etc.).
  • Type of Motors: Are the motors induction, synchronous, or other types (e.g., DC motors)?
  • Motor Control Needs: Define whether the motors require star-delta starting, direct-on-line (DOL) starting, auto-transformer starting, or variable frequency drives (VFD).
  • Automation and Monitoring: Determine whether remote control or automation will be required (e.g., through PLCs or DCS).
  • Protection: Specify the protection schemes needed, such as overload protection, short circuit protection, and ground fault protection.

2. Motor Control Selection

For each motor, select the appropriate method of control and protection based on its operational requirements. The common types of motor controls are:

  • DOL (Direct-On-Line) Starter:
    • Suitable for small motors (typically up to 5–10 HP).
    • Simple control involving a contactor and overload relay.
    • Direct connection to the power line for immediate full-speed operation.
  • Star-Delta Starter:
    • Used for larger motors (typically 10 HP and above).
    • Reduces the starting current by switching the motor windings from star to delta.
  • Auto-Transformer Starter:
    • Used for larger motors, reduces starting current more effectively than DOL but with better efficiency.
    • Suitable for motors with high starting torque requirements.
  • Soft Starters:
    • Used for smooth motor starting with gradual acceleration.
    • Limits inrush current and starting torque.
  • Variable Frequency Drive (VFD):
    • Used for precise motor speed control.
    • Allows for soft start, energy savings, and speed regulation.

3. Circuit Protection

Designing proper protection for each motor circuit is critical to prevent damage and ensure safe operation. Common protection devices include:

  • Overload Protection: Protects motors from running in overload conditions. This can be provided by overload relays or thermal overload protection built into the starter or VFD.
  • Short Circuit Protection: Provided by fuses or circuit breakers. A MCCB (Molded Case Circuit Breaker) is typically used for short-circuit protection.
  • Ground Fault Protection: If needed, ground fault protection can be implemented using a ground fault relay.
  • Phase Failure Protection: Detects a phase loss or phase imbalance in a three-phase system.

4. Sizing of Components

When designing the MCC circuits, it's important to correctly size the components. The typical components to size include:

  • Contactor: Should be selected based on the motor's full-load current (FLC). The contactor’s current rating should be at least equal to the motor's FLC.
  • Overload Relay: Should be sized for the motor's full-load current (FLC). The overload protection should typically be set at 115% to 125% of the motor’s FLC.
  • Fuses or Circuit Breakers: Should be rated for short-circuit protection. Typically, the circuit breaker or fuse should have a breaking capacity higher than the maximum fault current available at the location of the MCC.
  • Cables: Choose cables with sufficient current-carrying capacity and protection against heat and mechanical stress. The conductor size must be large enough to handle motor current and prevent excessive voltage drop.
  • Busbars: Busbars inside the MCC must be sized to handle the combined current rating of all motors connected to the MCC. Busbars are usually made of copper or aluminum and must have adequate insulation.

5. Control Circuit Design

The control circuits for the MCC are responsible for initiating and controlling motor operation. The components involved in the control circuits typically include:

  • Start/Stop Push Buttons: For manual control of the motors.
  • Contactors: Used for switching the power to the motors.
  • Overload Relays: To disconnect the motor if it exceeds its rated current.
  • Control Relays: For logic control, such as enabling multiple motors to operate in a specific sequence.
  • Indicator Lights: To show the operational status of each motor (ON, OFF, Fault, etc.).
  • PLC/DCS Integration: If automation is required, a PLC or Distributed Control System (DCS) will be integrated for control and monitoring.

Control circuits typically use low-voltage control transformers for safety and to reduce the risk of electric shock.


6. Electrical Drawing and Layout

After determining the components and sizes, the next step is to create detailed electrical schematics and layout for the MCC. These drawings will include:

  • Single-Line Diagram (SLD): Shows the power distribution for the MCC, including the motor connections, protection devices, and auxiliary components.
  • Wiring Diagrams: Include control wiring, interlocking wiring (for motor sequencing), and auxiliary wiring.
  • MCC Layout Diagram: Shows the physical layout of the MCC, including the arrangement of the components such as busbars, contactors, overload relays, VFDs, etc.
  • Control Circuit Diagrams: Represent the control wiring, including push buttons, relays, and interlocking logic.

7. Automation and Communication

In modern industrial facilities, MCCs are often integrated into a supervisory control and data acquisition (SCADA) system or controlled via PLC. These systems allow remote monitoring, control, and troubleshooting of motors. The following are considered:

  • Communication Protocols: Select communication protocols for integration, such as Modbus, Profibus, or Ethernet/IP.
  • Remote Control: Use remote start/stop functionality for operators to control motors from a centralized control room.
  • Automation: Implement motor sequencing, start/stop logic, fault detection, and performance monitoring via the PLC or DCS.

8. Safety Considerations

Designing an MCC circuit requires taking into account the safety of operators and equipment. Important safety considerations include:

  • Emergency Stop Buttons: Located on the MCC to quickly disconnect motors and stop operations in case of an emergency.
  • Lockout/Tagout (LOTO) Procedures: Provide clear procedures for isolating motors for maintenance, ensuring that workers cannot accidentally start the motor while working on it.
  • Grounding: Properly ground all equipment to prevent electric shock and damage to components.

9. Testing and Commissioning

After the MCC design and installation, the system must be tested and commissioned to ensure that all components are functioning correctly:

  • Functional Testing: Ensure the control circuits operate as expected, including start/stop, overload protection, and fault detection.
  • Protection Testing: Verify that circuit breakers, fuses, and overload relays are correctly sized and trip under fault conditions.
  • Motor Testing: Verify that motors start and operate as expected, including checking parameters like current, speed, and temperature.

Example of MCC Design Calculation:

Scenario: Design an MCC for controlling a 15 kW motor with a DOL starter.

  1. Determine the Full-Load Current (FLC) of the motor:

I=P3×VL×PFI = \frac{P}{\sqrt{3} \times V_L \times PF}

    • P=15 kWP = 15 \, kW
    • VL=400VV_L = 400V
    • PF=0.8PF = 0.8

I=150003×400×0.8=27.2 AI = \frac{15000}{\sqrt{3} \times 400 \times 0.8} = 27.2 \, A

  1. Circuit Breaker: The breaker size would typically be 125% of the FLC:

CB rating=27.2 A×1.25=34 ACB \, \text{rating} = 27.2 \, A \times 1.25 = 34 \, A

    • Select a 40 A circuit breaker (next standard size).
  1. Contactor: The contactor must handle the motor's full-load current (FLC) and should have a rating of at least 27.2 A.
  2. Overload Relay: Set at 115% of the FLC:

27.2 A×1.15=31.3 A27.2 \, A \times 1.15 = 31.3 \, A

    • Select an overload relay rated at 32 A.