Transformer Tests
Transformer Testing Used equipment:
1.1 Insulation Resistance Test (Megger Test)
• Purpose: Checks insulation health between windings and ground.
• Instrument Used: Megger (Insulation Resistance Tester)
• Test Voltage:
• LV Winding: 500V – 1000V
• HV Winding: 2500V – 5000V
1.2 Transformer Turns Ratio (TTR) Test
• Purpose: Ensures correct turn ratio between primary and secondary.
• Instrument Used: TTR Meter (Transformer Turns Ratio Tester)
• Acceptable Range: ±0.5% of design ratio
1.3 Winding Resistance Test
• Purpose: Measures resistance of windings to detect loose connections or damage.
• Instrument Used: Micro-Ohmmeter / DC Resistance Tester
• Test Current: 1A – 10A DC
1.4 Vector Group Test
• Purpose: Confirms correct vector group and phase displacement.
• Instrument Used: Phase Angle Meter & TTR Meter
1.5 No-Load Loss and Current Test
• Purpose: Measures core losses at rated voltage.
• Instrument Used:
• Power Analyzer
• Voltmeter & Ammeter
1.6 Load Loss and Impedance Test
• Purpose: Measures copper losses and impedance voltage.
• Instrument Used:
• Power Analyzer
• High-Voltage Source
1.7 Oil Dielectric Strength Test
• Purpose: Checks insulation quality of transformer oil.
• Instrument Used: BDV (Breakdown Voltage) Tester
• Standard Value: Minimum 30 kV for new oil
1.8 Magnetic Balance Test
• Purpose: Ensures uniform flux distribution in three-phase transformers.
• Instrument Used: Multimeter & Variac (Variable Voltage Supply)
2. Type Tests (Performed on One Unit per Batch)
2.1 Short Circuit Test (Dynamic & Thermal Stability Test)
• Purpose: Verifies the transformer’s ability to withstand fault conditions.
• Instrument Used: High-Power Short Circuit Test Setup
2.2 Lightning Impulse Test
• Purpose: Simulates lightning strikes to check dielectric strength.
• Instrument Used:
• Impulse Generator
• Oscilloscope
2.3 Temperature Rise Test
• Purpose: Measures winding and oil temperature rise during full load.
• Instrument Used:
• Thermocouples
• IR Camera
3. Special Tests (As per Customer Request)
3.1 Partial Discharge Test
• Purpose: Detects internal insulation defects.
• Instrument Used: Partial Discharge Detector
3.2 Sweep Frequency Response Analysis (SFRA) Test
• Purpose: Detects winding displacement or mechanical deformation.
• Instrument Used: SFRA Analyzer
3.3 Frequency Response Analysis (FRA) Test
• Purpose: Checks mechanical integrity of windings.
• Instrument Used: Frequency Response Analyzer