Substation Layout
1- Types of Substations
Electrical power plants
are generally constructed far from the centers of electrical loads due to the
economic feasibility of establishing the plant. In order to transmit electrical
energy over long distances, the voltage is raised to reduce the losses in the
power lines, but when this energy is used, the voltage must be reduced again to
adapt to the electrical loads. Transformer stations are generally divided into:
1.
Transformer stations to
raise the voltage of the generator in the generating stations through step up transformers , and the transformers are called machine
transforms because of their connection to the generator. Most of these
transformers contain two coils, where the transformer coil connected to the
generator is connected in the form of a delta, and on the network side (the
other coil) is a star (Star) and the tie point (Star point) is directly
connected to the ground (Solidly earthed).In some cases (relatively few), the
converter has three coils in order to obtain two different voltage values.
Also, the impervious equivalence point of the transformer may be connected to
the ground.
2.
Network Transformer Substations
These stations contain transformers to reduce the voltage -
but it does not yet reach the distribution voltage - and autotransformers may be used in these stations because of their economic feasibility, and
these transformers may give one or two values of voltage in the secondary
circuit according to the number of coils.
Electrical power grids usually contain another set of
transformer stations to reduce the voltage again – but it does not yet reach
the distribution voltage – for example, 220/500 kV transformers and 220/66 kV
transformers, and the locations of these stations are selected according to the
distribution of the electrical load centers.
C- Distribution Substations Distribution networks start with distribution
transformer stations, which are stations to reduce the voltage for a second
time (step-down transformer) and from
the secondary circuit of the transformers, the power lines extend to the distribution transformers, from which the secondary feeder lines for the end user come out Electrical loads are
divided in terms of the nature of consumption into industrial loads, commercial
loads, residential loads , and special
loads that require requirements that must be met in the source of electrical
supply for them.
In
terms of construction features, transformer stations are divided into:
1.
Outdoor Substation
2.
Indoor Substation
3.
Underground Substation
4.
Hanging stations,
whether open or in a Pole mounting booth
- Open or Kiosk
The type of station
depends on the voltage conversion ratio, economic factors, the capacity and
nature of the place, safety measures, and others. Figure 1 shows a diagram of a transformer
station within a building.
Figure
(1)
Mobile Substations
Despite the
considerations of protection and backup,
the collapse of the feeder buildings,
transformers, or both may occur in the transformer station, which causes the
power supply to be completely cut off for a period of time, in this case, a
mobile transformer station can be used, all its devices are mounted on large
tractors with a Large Tractor Trailer,
and in general, the capacity of these stations does not exceed 40 MVA - this
causes considerations of size and weight of the movement, and this station can
be equipped within three to six hours. Shape No. (2) shows an example of this
type of transformer station.
Figure
(2): Portable Transformer Station
2- Civil and Electrical Works for Transformer Stations
Civil and Electrical works in Substations
2-1 Civil works
include:
1.
Buildings, whether residential or non-residential
(offices, warehouses, repair workshops, control galaxies, etc.)
2.
Railways and Suspended
Cranes
Railway track and overhead
cranes cable trenches
3.
Cable Walkways
4.
Roads and Trails
5.
Fencing Cutting Devices Protection Fence
Around Switch yard
2.2 Electrical Works
- 1. Choosing the arrangement of the distribution bars Bas Bar arrangement
- 2. Selection of Isolators
- 3. Selection of Instrument Transformers
- 4. Choosing Circuit Breakers
- 5. Lightning arrestors
- 6. Choosing Power Transformers
- 7. Protective relaying schemes
- 8. Choosing Voltage regulating equipment
- 9. Cable Selection
- 10. Choosing Earthing Systems
- 11. Illumination System Selection
- 12. Choosing Fire Protection System
- 13. Communication Systems Selection
- 14. Selection of Auxiliary Supply
- 15. Choosing Interlocks for Regulation
In general, the design
of the transformer station should achieve flexibility , simplicity, low economic cost with high
quality performance.
3- Electrical layout of substation
The electrical pattern
of the substation shows the method of arranging the distribution rods and the
relative places of the devices and connecting them with lines, and this diagram
may also be called a key diagram . While
in the civil diagram, the devices are illustrated while maintaining the
distances and angle of inclination with an appropriate drawing scale. Figure
(3) shows an example of a transformer station.
Figure (3): Transformer
Station
4- Bus Bars
Distribution rods are one of the most important
components of the stations, as they pass through high electrical power and any
malfunction in them causes power interruption, so the quality of the electrical
design must be taken into account. and the structural aspect of the
installation to withstand the forces exposed to it.
4.1 Types of Distribution Rods
There
are two main types:
1. Steel Rod Rigid bus
2. Strain bus
Rigid rods are usually
used in the case of medium and low voltage, and they are made of aluminum or
copper in the form of bars or tubes, and they are used for fixing and
insulation, and in the case of high voltage, flexible rods made of stranded and
reinforced aluminum wires are used or of copper, and they are installed on strain
type insulators.
4-2 Bus conductor material
The choice of the
material from which the rods are made depends on several factors, which are:
1.
The value of the loss
in the allowable voltage
2.
Loss of electrical
power
3.
Passing Current
Capacity
4.
The value of the Qasr
Stream
5.
Metal corrosion
6.
Dynamic wind load and
static load of accumulated snow
In general,
heat-treated aluminum, copper, and aluminum alloys are used, especially in the case of high-voltage and
ultra-high voltage pipes.
Aluminum is
distinguished from copper in that it is less in weight. It also requires less
maintenance, and if it has a certain current capacity and a permissible
temperature rise, the aluminum conductor section is about 33% larger than the
copper conductor.
4.3 Common bus bar arrangement
4.3.1 Single bus bar
Figure 3 illustrates an
example of this case.
4.3.2 Single bar
with single bus bar divider with bus
sectionalizer
The single rod is characterized by simplicity and low costs when implementing, and to increase the degree of reliability, it can be divided into parts – usually only two parts – as in Figure (4). Each part is connected to a feeder and on the other hand electrical loads are connected. To increase efficiency, it is preferable to use circuit breakers to separate the parts, rather than using an isolator breaker, as there can be a difference in voltage between the two parts, so that current passes through the connection.
Figure
(4): Single rod with divider
4.3.3 Double bus bar
To increase the degree of reliability and with
the possibility of increasing the cost, dual rods are used, and the operation
is as follows:
1.
Loads are distributed
on the rails
2.
The loads are divided into groups and each set
is fed from the rod
3.
Maintenance can be done for one rod without
cutting off the current to the loads by transferring it to the other rod
Figure (5) shows how to
connect the two rods to a bus coupler
circuit breaker to transfer loads from one rod to another, since the separation
knife cannot cut off the load current. When performing maintenance of the
cutting devices, the feed must be disconnected. This system may call two rods
with a single bus bar.
1.
Double
bus bar double circuit breaker
Figure (6) shows a diagram of this system
which is considered to be high cost. Therefore, its use in transformer stations
is relatively small and it is used in large transformer stations.
2.
Double
Rail and One and a Half Circuit Breaker
Double bus bar one and half circuit breaker
Figure (7) shows a
diagram of this system and shows the savings in the number of cutting devices,
for every two circuits there is one spare breaker. This system requires complex
protective devices and is therefore not commonly used.
Figure
(5): Two-rail system
Figure (6): Dual Rails and Pieces
Figure
(7): Two-rail, one-and-a-half cutting device
4.3.6 Main and transfer bus bar
The diagram shown in
Figure (8) allows for maintenance of the cutting devices, but more isolators are used and care is required when moving from one rod
to another.
4.3.7 Two rods with
side separator
Figure (9) shows the
diagram of this system, which is a mixture of a two-bar system, a basic rod
system, and a conversion rod. Maintenance of cutting devices is allowed, but
more separators are used. It is characterized by simplicity in operation. For
maintenance, the feeder can be cut off briefly, for example during the period
of light loads, during which the transfer is carried out while avoiding placing
the separators on a single circuit.
4.3.8 Mesh or ring
scheme
The diagram shown in Figure (10) shows the
arrangement of the separator and cutting devices, which is characterized by the
following:
1.
Allows dual feed per
circuit
2.
Allows maintenance of
cutting devices
3.
Lower cost than a
bi-rod system
It is recommended that
the number of circuits fed by the system should not exceed 6 circuits, so it is
not suitable in the case of networks in which expansion is underway.
Figure (8)
Figure
(9): Two rods with side separator
Figure
(10): Network or Loop Diagram
5
- Transformer Stations in Distribution Systems
Figure (11) shows the simplest picture of a
distribution station, where the station is fed by one main distributor and
shows the breaker device and the separation equipment, and the disconnect
switch of the cutting device can be omitted in terms of electrical load,
although it is preferable to place the disconnect switches before and after the
cutter.
Figure (12) shows a transformer station containing two
transformers, each transformer is connected to an independent feeder, and the
transformer capacity is 75% of the station's capacity. This system is
characterized by a relatively short yar value and the existing load disconnect
switch connected to the distribution rod is closed only if one of the switches
on the transformer's secondary coil is in the open position.
Figure (13) shows a transformer
station with a higher economic cost and a higher degree of dependence. The
station has cutting devices connected to the distribution rod as well as the
terminal of the transformer secondary coil and the system works automatically
to ensure continuous feeding.
Figure (13)
0 Comments