Three-Sided Electrical Transformer
Introduction
Electrical power is generated in the form of
three-phase voltages with values up to 13 kV and sometimes up to 35 kV, and
energy is transmitted on high-voltage lines and cables with values up to 220,
500 and sometimes up to 750 kV, thus the need for three-phase transformers
appears to raise the value of the generation voltage to the transmission
voltage and also to reduce the transmission voltage to the distribution voltage
values that reach 66 and then to 11 kV.
In the case
of electrical systems with 380 V tri-directional voltage values, the
three-phase transformer has emerged as an alternative to the use of three
single-sided transformers, which were commonly used in the past due to
operators' lack of experience with tri-directional transformers. One of the advantages of using three-sided
transformers is that they require less space, less weight, and a 15% lower cost
compared to three single-sided transformers.
2- Installation of three-sided transformers
Three-sided
transformers are similar in terms of installation quality to the two types of
single-sided transformers with a core or
shell type. Figure (1) shows the basic
structure of a trihedral transformer, where the initial coil connected in the
shape of a star is shown by a trifacial source. The core of each face is 120
degrees apart from the other, and the legs are in contact with each other. It is noted that this middle leg
carries a magnetic field proportional to the sum of the facet currents IR+IY+IB.
Since the sum of these currents of balanced systems is equal to zero, there is
no need for this intermediate man.
In
this case, either of the two hearts acts as a complement to the third heart
magnetic field path, and this is similar to the distribution of currents in the
three-point systems.
Figure
(2) shows the development of the three-sided transformer and the three coils in
the form of rectangles, and it is observed that the magnetic field , shown at a
given moment in time, is distributed between the three cores according to the
three-phase system. Figure (3) shows the coils in a cylindrical shape around
the iron core.
Figure (1)
Trifacial coil envelope transformers are similar to unifacial
ones of the same type. The three three-sided uniconverters can be combined to
form a three-sided transformer, but the ferrous material can be provided with
the design shown in Figure (4).
The saving of the ferrous material is
represented by the combined use of magnetic flux pathways. The three faces are
a little more independent than the heart transformer, because each face has an
independent magnetic circuit.
Figure (4)
There is a disadvantage in the tri-sided converter that if one
of the faces is lost, the converter needs to be turned off, and the
tri-encapsulated converter can be excluded when connecting files in a delta
image but technically it is not convenient. It is noted that in the case of the
three single transformers, the damaged transformer can be excluded without
affecting the overall function.
Example (1):
A 3-phase, 50-Ht transformer has a delta-connected primary and
star-connected secondary, the line voltages being 22,000 V and 400 V
respectively. The secondary has a
star-connected balanced load at 0·8-power factor lagging. The line current on
the primary side is 5 A. Determine the
current in each coil of the primary side is 5 A in each secondary line. What is the output of the transformer in k W?
Solution. It
should be noted that in three-phase transformers, the phase transformation
ratio is equal to the turn ratio but the terminal or line voltages depend upon
the method of connection employed. The ∆ / Y connection is shown in Fig. (1).
Fig. (1)
Phase voltage on primary side = 22.000 V
Phase voltage on primary side = 400 / √3
K = 400/22,000 x √3 =
l/55√ 3
Primary phase current =
5/√3A
Secondary phase current =
275 A
Secondary line current =
275 A
Output =
√3 VL IL cos f
= √3 x 400 x 275 x 0.8 = 152.42 kW
Example (2):
A 3-phase, 3,300/400-V transformer high-voltage winding
connected in delta and the low-voltage connected in star. If a load consisting
of three-impedance 6+j8 ohm is joined in delta across the low voltage side,
calculate (a) the kW delivered to the kW delivered to the load (b) currents in
the low and high-voltage windings and the current drawn by the transformer from
line. Neglect losses and no-load current of the transformer.
Solution. The
transformer connection diagram is shown in Fig. (2).
Fig. (2)
Power delivered to the load = √3 VL IL
cos f
Now, consider the D -connected load
Vph=VL=2400 V Zph = √( 62 + 82)=
10 W
Iph = 400/10= 40 A IL = √3 x 40 = 69 · 3 A
cos f = 6/10 =0·6
P= √ 3 x 400 x 69· 3 x 0· 6 = 28,807 W
(b) Primary phase voltage = 3.300 V
Secondary phase voltage =
400 / √ 3
Current in low-voltage winding i.e. secondary is I2
= 40 x √3 = 69.3A
Current in low-voltage winding i.e. secondary is I1=KI2=
4.85 A
0 Comments