Failures in electrical power systems
1- Faults in electrical power systems:
Modern power systems are designed
with a high level of reliability and flexibility, allowing one or more elements
to be taken out of service with minimal disruption. However, breakdowns in
electrical insulation or equipment may still occur. These failures may result
from electrical, mechanical, or thermal breakdowns—or a combination of
these.
Table 1 summarizes the main types and causes of failures in
electrical systems.
Table (1): Types and General Causes of Collapse
|
Type |
Causes |
|
Insulation
|
|
|
|
Electrical |
Lightning, transient waves from switching operations, sudden voltage spikes |
|
|
Thermal |
failure of cooling medium, current surges, voltage increases, high ambient temperature |
|
|
Mechanical |
High current forces, earthquakes, foreign object collisions, ice or snow loads |
Consequences of Faults
Malfunctions in power systems can
lead to several consequences, including:
- Abnormally high currents flowing through system
components, causing excessive heating.
- System voltages deviating from normal and acceptable
ranges, risking equipment damage.
- Unbalanced operation of three-phase systems, leading to improper equipment performance.
2. Types of Faults
Electrical faults are generally
classified into two main categories:
- Open-circuit faults
– caused by the opening of one or more lines.
- These faults do not generate high fault currents.
- Single-phase loads may continue to operate, but
three-phase loads lose supply.
- Protection relays are needed to detect such faults.
- Short-circuit faults
– caused by contact between one or more phases and ground, or between two
or more phases without ground.
- These faults typically result in very high currents.
- They create thermal and mechanical stress on
network components.
- They may also cause disturbance in communication
and control systems.
Common Types of Short-Circuit Faults
- Three-phase fault (with or without ground)
- Phase-to-phase fault
- Double-phase-to-ground fault
- Single-phase-to-ground fault
Simultaneous faults in two parts of a system are difficult to detect accurately, but they are rare and not usually a major cause of incorrect operation.
3- Characteristics of faults
3.1 Fault Angles
The power factor (angle) of the
fault current depends on the electrical source and circuit parameters up to
the fault location.
- For ground faults, the power factor is
influenced by the grounding method of the system.
- Typical fault angles are:
|
Voltage
Level |
Typical
Fault Angle (Lagging) |
|
7.2 – 23 kV |
52° – 54.5° |
|
23 – 69 kV |
54.5° – 57.5° |
|
69 – 230 kV |
60° – 80° |
|
230 kV and above |
75° – 85° |
Note: If transformer and generator impedances dominate, the
fault angle will be higher. If cables contribute significantly to total
impedance, the angle will be smaller.
3.2 Grounding of the electrical system
Grounding the electrical system affects both the value and angles
of ground faults, and there are three ways of grounding:
1- Ungrounded
(Neutral Point Isolated)
- Equivalent to grounding through phase-to-ground
capacitances.
- During a single line-to-ground fault, voltages of the
unfaulted phases increase.
2- Grounding
is done during resistance (resistance or reactance)
- Limits fault current by inserting resistance/reactance
between neutral and ground.
3- Effective grounding system (the neutral
point is directly connected to the ground)
- Neutral point is directly connected to ground.
- Single line-to-ground faults cause large currents,
but voltage rise in unfaulted phases remains small.
The ungrounded system can be considered to be grounded by equal ground capacitors (Figure 1), and in identical electrical systems where the three capacitors to the ground are equal (N-E), and when a face grounding occurs (A), the displacement triangle will appear as in Figure (1). Consequently, Vbg and Vcg will be approximately =
of their natural original value.Figure (1): Voltage Diagram for Shortening the Face of the Earth in
an Ungrounded Electrical System
Conversely, in the case of a short circuit of one of the aspects of
the radiological system with direct grounding, this will lead to a large short
current in the case of ground failures, with a very small increase in the
voltage of the non-short circuit faces.
Figure (2): Voltage vector to shorten the face of A to
the ground
3-3 Fault resistance
- Short circuits are often accompanied by arcs.
- Arc resistance varies with arc length and affects the fault current magnitude.
- For phase-to-phase faults, arc resistance usually has little effect (except at low voltages).
- For ground faults, arc resistance is more significant because arcs may be long and tower footing resistance adds to total impedance.
3-4 Deformation of faceted efforts during failures:
During faults, system voltages and currents become unbalanced.
- The largest voltage drop occurs at the fault location.
- Voltages between the source and fault point vary depending on the measurement location.
- Assumption: Z1 = Z2 = Z0 (positive, negative, and zero sequence impedances are equal).


0 Comments